Medium Gases Device type Compact flow device Device design Compact device including sensor (permanently mounted), Compact device including sensor (remote) Flow range 0,1 ... 30 m/s (optionally available up to 200 m/s) Flow accuracy ±5% of the measuring range end value, Reproducibility ±2% of full scale value Display LCD with switchable backlight, Yellow LED for flow velocities > switching point, Green LED during operation, 10 red LEDs for the flow velocity in 10% steps Switching point Stepless adjustment (software or potentiometer) Protection class evaluation unit IP66 Protection class sensor IP67 Special features Linear analog output Flow velocities up to 200 m/s measurable, acknowledgeable alarm, steel housing available on request, adjustable start-up delay 0 ... 300 s Velocity dimensions: m/s, l/min, m³/h, linear analog output can be used up to 350°C media temperature, flow velocities up to 200 m/s measurable, steel housing available on request, acknowledgeable alarm, adjustable start-up delay 0 ... 300 s, velocity dimensions: m/s, l/min, m³/h Output signal Switching output, Analog output Switching output specification 1 NO contact (closes/opens with flow, adjustable) Sensor break output signal Fault-specific error codes in the LCD, 4 mA, Relay drops out Sensor short-circuit output signal Fault-specific error codes in the LCD, 4 mA, Relay drops out Relay output specification 1 NO contact (closes/opens with flow, adjustable) Immersion depth 50, 130, 165, 300, 400, 500, Special lengths on request Process connection PG7, optional G1/2-inch, G1/4-inch by means of reducer Housing material Polycarbonate, UL94-V0 Sensor material MS58, nickel-plated (optionally available in stainless steel) Pressure resistance 10 bar Housing dimensions 80 mm x 113 mm x 60 mm Power supply 20 ... 30 V DC Electrical connection 9 terminals (max. 1.5 mm²) Max. power consumption 5 VA Current and contact rating 175 V AC/DC, 0,25 A Minimum switching capacity 10 mA, 5 V DC Ambient temperature -20 ... 60°C Optimal inlet path >10 DN Optimal outlet path >5 DN Temperature gradient 30K/min Certificates CE ATEX certification keine SIL level keine Country of origin Germany Customs tariff number 90 26 80 20 HS code 90 26 80
|